Application The current transformer is designed for current,power measurement and relay protection in AC power system with rated frequency 50Hz,rated voltage 0.5KV and below. Service condition Altitude:up to 1000m above sea level Ambient temperature:-5 to+40℃ Relative humidity:85%,at 20℃ Construction The current transformer is bus type and cast-resin insulated,The seconday windings are wound on the core.The base plate is located at the botton for mounting. Type meaning |
|
Technical data Performance conforms with IEC standard and GB1208-97"Current transformer". Main technical data |
Type
|
Rated primary current(A) |
Rated secondary current(A) |
Primary ampere-trun |
Rated secondary burden cosφ=0.8(VA) |
Primary current required by multi-turn primary winding (A) |
Class0.5 |
Class 1 |
Class 3 |
LMZ1-0.5 |
5、10、20、50、100 15、30、75、150 40、200、300、400
|
5 |
100 150 200 300、400 |
5 |
7.5 |
|
5-50 15-75 40 |
LMZJ1-0.5 |
5、10、20、30、50、75、100、150、300、40、200、400、500、600、800 |
5 |
300 400 500-800 |
10 |
15 |
|
5-150 40-200 |
1000、1200、1500、2000、3000 |
5 |
1000-3000 |
20 |
30 |
50 |
|
|
Overall dimensions
Type |
Current ratio (A) |
H(mm) |
h(mm) |
φD(mm) |
φd(mm) |
Weight(kg) |
LMZ1-0.5 |
5-200/5 |
120 |
70 |
92 |
30 |
0.9 |
300/5 |
125 |
75 |
97 |
35 |
400/5 |
125 |
75 |
97 |
45 |
LMZJ-0.5 |
5,10,15,20,30,50, 70,100,150/300/5 |
130 |
75 |
106 |
35 |
1.0 |
40,200,400/5 |
135 |
45 | | |